UPS and lithium battery joint test-CAN communication test

SCU Lithium Battery & UPS joint test.

Equipment:

600kw Modular UPS Rack, 1set;

75kw UPS Power Module, 4units; 

Battery:+-240V80Ah 38.4kWh 4C Lithium-ion LFP Battery, 2sets.

Test:

Lithium Battery CAN Communication Fail

?Disconnect the CAN cable between UPS & Lithium Battery

?Alarm, UPS keep charging and discharging according to preset plan.

?Recover the CAN cable, Alarm clear, UPS charging and discharging as Battery demand again.