UPS and lithium battery joint test-CAN communication test
Vivian Zhang
Vivian Zhang
International Business Director, Modular UPS | Data Center | EV charger | ESS | Sicon Chat Union Electric Co.,ltd
SCU Lithium Battery & UPS joint test.
Equipment:
600kw Modular UPS Rack, 1set;
75kw UPS Power Module, 4units;
Battery:+-240V80Ah 38.4kWh 4C Lithium-ion LFP Battery, 2sets.
Test:
Lithium Battery CAN Communication Fail
?Disconnect the CAN cable between UPS & Lithium Battery
?Alarm, UPS keep charging and discharging according to preset plan.
?Recover the CAN cable, Alarm clear, UPS charging and discharging as Battery demand again.