Trips, interlocks, permissives, and sequences

Trips, interlocks, permissives, and sequences

Trips, interlocks, permissives, and sequences


are fundamental concepts in instrumentation control systems such as ESD (Emergency Shutdown), DCS (Distributed Control System), and PLC (Programmable Logic Controller). Here's a summary of each concept:


Trip:

A trip is an action initiated by the control system that forces a device or devices to a predetermined state. Trips are often related to safety functions and are typically initiated by a Safety Instrument System (SIS) or a hardwired system. However, in some cases, PLCs or DCS may also initiate trips if they meet the necessary independence and safety integrity level (SIL) requirements. Examples of trip signals include closing a valve, opening a valve, stopping a motor, etc. Once a trip is activated, the devices remain in the specified state until manually reset by an operator. Trips are usually controlled procedures and can only be reset if certain conditions are met.

Interlock:

An interlock is similar to a trip but is considered a "self-resetting" trip. Interlocks are typically used for on/off control and are not usually classified as safety-related. They are often initiated by DCS or PLC systems. However, if an interlock has safety implications and meets the required SIL rating, it may be implemented in an SIS or hardwired system. Like trips, interlocks force devices to predetermined states (e.g., closing a valve, stopping a motor) but automatically remove the interlock when the initiating cause returns to a healthy condition. Interlocks can usually be overridden for operational reasons or defeated for maintenance purposes.

Permissive:

A permissive is a specific type of interlock used to prevent actions from taking place until certain criteria are met. Permissives are typically initiated by DCS or PLC systems, but if they have safety implications and meet the required SIL rating, they may be implemented in an SIS or hardwired system. Permissives ensure that predefined conditions are satisfied before allowing an action to occur. For example, a permissive may prevent a pump from starting until the suction valve is open. Once the permissive conditions are met and the action is executed, the permissive becomes inactive. Permissives can usually be overridden for operational reasons or defeated for maintenance purposes.

Sequence:

A sequence refers to a prearranged set of actions carried out by the control system. Sequences can be initiated by events or operator actions. They can be either "single pass" or "cyclic." A single-pass sequence involves a series of actions performed once, based on a specific trigger or operator command. For example, an agitated vessel reaching a predetermined level may trigger a sequence that stops the feed pump, closes the filling valve, stops the agitator, and then opens the discharge valve after a 30-second wait. A cyclic sequence, on the other hand, involves actions that repeat based on certain conditions.

Aziz benamor

Process Design Engineer

2 个月

Insightful.

回复
Umashankar AB

Senior Manager - Automation at Desmet Engineering Center Pvt. Ltd.,

1 年

Thanks for the interesting information. I am curious to know if this information is defined as standard practice in any of ISA, IEC or any other standard ?

要查看或添加评论,请登录

Ahmed Samir的更多文章

  • how to start the fired heater?

    how to start the fired heater?

    To start a heater, follow these steps: Check start permissives: Verify that all start permissives or interlocks are in…

    2 条评论
  • compressor start up

    compressor start up

    To start a compressor safely and efficiently, the following steps should be taken: Purge the compressor loop with…

    1 条评论
  • field operator

    field operator

    The responsibilities of a field operator in a plant include: Monitoring and inspection: Checking rotating equipment for…

  • hand over a pump to maintenance

    hand over a pump to maintenance

    These steps outline the necessary procedures to ensure the safety and proper handling of the pump during maintenance…

  • If you have a flow control valve issue after the pump, here are the steps you can take:

    If you have a flow control valve issue after the pump, here are the steps you can take:

    1-Check the pump: Verify that the pump is functioning correctly. Ensure it has power, the motor is running smoothly…

社区洞察

其他会员也浏览了