Top 5 Reasons HVAC Coils Prematurely Fail

Top 5 Reasons HVAC Coils Prematurely Fail

  1. Coil Plugging: If filters are not changed or your coil cleaned properly in a timely manner, your coil will actually act as a filter. When dirt builds up on the coil, it will prevent heat transfer and can cause a 20% to 40% drop in performance. Dirt adds to the coil resistance and will absolutely cause your coil to fail prematurely.
  2. Vibration: When your coil is installed near a moving piece of equipment, vibration can occur and cause leaks. The area where these leaks occur is very important and will clue you in to if the problem is vibration. If they are near the tube sheet and look like they are slicing through the tube, the coils should be isolated from the rest of the system to prevent vibration from causing damage. One way to combat this is by oversizing the tubesheet holes, but many manufacturers will not do this. Condenser coils are usually the most common victims of vibration.
  3. Corrosive Environment: This applies to both the air in the environment and inside the tubes. For instance, if there is something in the air that is corrosive, it will eat away at the copper tubes whether you have 0.020” wall or 0.049” wall. This is very common in areas where there may be salt in the air. To keep the costs down from going to a stainless steel or cupro-nickel coil, we usually suggest coating the coil. Coatings are almost always within the budget and only add about a week to the lead time. Steam condensate and untreated water can cause corrosion within the tubes of coils as well. If you have a steam coil that has failed before the one year warranty, there’s a great chance corrosive agents are in the steam and it’s eating away at the copper tubes.
  4.  Freeze-Ups: Most people think that when a coil freezes, the water or condensate laying in the coil freezes into ice and it expands causing the tubes to bulge and eventually spring leaks. What really happens is the coil will freeze in multiple areas simultaneously and it’s the pressure between these areas that cause the tubes to swell and eventually burst. These are very easy to spot as the leaks will run the length of the tube rather than around the tube. 
  5.  System Design: You would be amazed how many coils were never properly designed for their systems. If there was a problem with design, replacing the coil will only duplicate the problem. A high percentage of all our projects were because the coil was built incorrectly or was never designed right in the first place. Sometimes, owners want to improve performance by adding a couple rows, but don’t consider the air pressure drop or fluid pressure drop that comes with it.

When dealing with a coil manufacturer, partner up with one who will walk you through the engineering and explain it along the way. Capital Coil & Air has well over a 50 years of experience and has seen every issue to make sure your everything from the quote to the installation go smoothly! Give us a try on your next project! www.capitalcoil.com

Mr. Kelly Sprayberry, P.E.

Employee at Seasons 4, Inc.

6 年

What are your thoughts on formicary corrosion? About 10 years ago it seemed like there were an inordinate amount of claims of leaky coils, the ones we had were sent back to a supplier who claimed that was the issue. We’ve had very few of any. I can’t help but think it was a bad batch of copper tubing