During Covid we saw a big push for better filtration of facility air. Some facilities switched to tighter, higher MERV, filters without understanding the ramifications this would have on their HVAC equipment. Today we are going to cover what happens to your HVAC equipment when switching to a higher MERV rated filter. We are also going to you how you can improve your filters without damaging your equipment.
EFFECTS OF HIGHER MERV RATED FILTERS ON HVAC SYSTEMS
It’s important to understand that sliding in a tighter filter and walking away isn’t the right fix. Blower motors are designed to meet a certain static load and can’t always overcome a tighter filters restrictions on air flow.
If you were to throw in a high MERV filter, without adjusting anything else, you’ll increase the pressure drop across the unit. This is because, without changes, the motor can’t overcome the tighter filter. This reduces the airflow through the unit, causing a cascade of problems.
If we have lower airflow across your heat exchanger, that we are blasting a hot flame into, the heat exchanger temperature begins to rise. This means our heat exchanger is running hot and you will eventually burn holes in the heat exchanger. Additionally, your motor will also begin to heat up as there is less airflow and it struggles to keep up.
“85% motors that get sent back to Johnstone Supply are from a winding failure from getting to hot. This is caused from restrictions in airflow.” – Jason Carlson – VP of Training, Johnstone Supply
On top of this, your HVAC unit now has to stay on longer to deliver the same amount of air. This decreases the units efficiency. So what can you do?
SOLUTIONS FOR IMPROVED AIRFLOW
If you want to use a tighter filter, there are three primary solutions to maintain proper airflow:
Note: Failing to rebalance your equipment after changing to a tighter filter means you’re knowingly restricting airflow. Over time you will cook the heat exchanger or the motor if adjustments aren’t made.
THE ROLE OF ECM MOTORS
Electronically Commutated Motors (ECMs) are now common in modern HVAC equipment. These motors are controlled by a control panel that adjusts fan speed to compensate for loss in airflow. They contain a module that measures static pressure and adjusts speed based on demand. While this can protect the heat exchanger if filters get plugged up, ECM motors become extremely inefficient at higher ranges. They also often can’t handle the increased restriction caused by tighter filters.
Newer units equipped with ECM motors may ramp the motor down to half speed if they detect a static pressure over 0.8. This protects the motor from overheating but also means the unit won’t run unless you make modifications to your system.
UNDERSTANDING MERV RATINGS
The Minimum Efficiency Reporting Value (MERV) tells us how tight a filter is or how small the particles it can capture. MERV ratings range from 1 to 20.
As the rating increases, the minimum size of the particles filtered out gets smaller, meaning more particles are captured. Here is a breakdown of MERV ratings and the particles they filter:
领英推荐
While higher MERV ratings are effective at capturing smaller particles, they also create more resistance. This can lead to reduced airflow and potential damage to your HVAC system. For instance, MERV 8 filters catch larger particles and are less restrictive, while MERV 11 filters catch smaller particles and are more restrictive. This means?MERV 11 filters not only have higher initial resistance but also build up additional resistance faster as they capture more debris.
FILTER COMPARISON: MERV 8 VS. MERV 11
MAINTENANCE TIPS WHEN SWITCHING TO A HIGHER MERV RATED FILTER
When switching to a higher MERV rated filter, it’s crucial to follow some maintenance tips to ensure your HVAC system runs efficiently:
COST IMPLICATIONS OF HIGHER MERV RATED FILTERS
While the initial cost of the filter might be higher, there can be additional costs associated with maintaining proper airflow and system efficiency. This might include:
FREQUENTLY ASKED QUESTIONS
Q: DO HIGHER MERV FILTERS RESTRICT AIRFLOW?
Yes, higher MERV filters are more restrictive and reduce airflow. If you make adjustments to the HVAC system it can eventually handle the increased resistance.
Q: CAN HIGHER MERV FILTERS DAMAGE MY HVAC SYSTEM?
If not properly managed, high MERV filters can cause increased pressure drop, leading to overheating and potential damage to the heat exchanger and motor.
Q: HOW CAN I IMPROVE FILTRATION WITHOUT DAMAGING MY HVAC SYSTEM?
Solutions include increasing the filter area, adjusting motor speed, or installing a new motor with higher horsepower.
NEED HELP SWITCHING TO A HIGHER MERV RATED FILTER?
Reach out to us via email at [email protected] or give us a call at 800-237-3154.