Steam Piping
Effectively steam can be transported through pipe lines to the point of use. Due to reduction in volume due to condensation or utilization from the steam piping network, results in a localized reduction in pressure. This pressure drop through the system creates the flow of steam through the pipes.
Steam at high pressure occupies a lower volume than at atmospheric pressure. The higher the pressure, the smaller the bore of pipework required for distribution of a given mass of steam. Steam velocity in conduit can be considered from 15m/s to 40 m/s based on the pressure. Steam at atmospheric pressure like flash steam at 15 m/s and steam at 3.5 bar at 25m/s and 10 bar and above at 40m/s.
Steam piping are normally insulated with mineral wool for reducing the heat loss and prevention of incident for accidental touching of surfaces. The optimal lagging thickness decided based on the steam temperature, thermal conductivity of piping material and insulation material and environmental condition of the surface. Due consideration shall be considered for convective heat transfer usually in open environment.
The condensate form during transportation must be removed as early as possible from the lowest point in the segment due to following reason.
The steam should be as dry as possible to ensure it is carrying heat effectively. Steam traps are provided to drain the condensate from the piping and prevent steam to escape. There is various type of steam traps used based on the application and economy. Most commonly used traps are as below.
The condensate which forms will drain easily through a steam trap and sent back to boiler feed water tank through condensate drain piping. If it is contaminated by process fluid, it will be sent to drain. This saves valuable heat energy also saves on water and water treatment costs.
To effectively transporting the condensate back to boiler feed water tank steam operated mechanical power pumps are usually used.
?
Steam separator are used in the piping to remove moisture from the steam. Usually this contains a series baffles which interrupt the path of the steam. The steam hits the plates, and any drops of moisture in the steam collect on them, before draining from the bottom of the separator.
Important Design Consideration:
Condensate from steam line should be drained at regular interval usually in every 30 -50 m. before the expansion loop, sudden change in elevation, before entering a equipment.