SPT12_Power Transformers, Breather

SPT12_Power Transformers, Breather


Let's talk about an accessory, which sometimes is not given much attention; but it has great importance, the “Breather” ??

Why do we use it?

The service life of transformers is closely related to the service life of the oil-paper insulation system; the reason is that if the mechanical stability of the oil-paper insulation is lost, there is a risk of electrical failure and, consequently, general failure of the transformer.

There are different measures in this regard, but there are two that allow avoiding external influence, such as the conservative and the breather.

Focusing on the Breather ??, the one we know as the type has commonly been used “Silica Gel Breather”

When an electrical power transformer is loaded, the temperature of the transformer insulating oil increases, consequently the volume of the oil is increased. As the volume of the oil is increased, the air above the oil level in conservator will come out. Again at low oil temperature; the volume of the oil is decreased, which causes the volume of the oil to be decreased which again causes air to enter into conservator tank

Note that natural air contains moisture that can mix with transformer oil and harm its insulation. It is crucial to filter this moisture out. A silica gel breather is the most common method for this purpose.

Silica gel breather for transformer is connected with conservator tank by means of breathing pipe. It is a container filled with silica gel that air passes through. Silica gel absorbs moisture very well ??

Silica gel crystals change color; note that the color of the silica gel crystals is generally used as an indicator of when the silica should be replaced. It is dark blue when dry; when the gel absorbs moisture and becomes saturated ?, the color changes to pink (see Figure 1).

Adsorption capacity ?over a period of 3 – 12 months, after that the Silica Gel ?must then be replaced ??

?Why? Due to as the silica gel will be completely saturated with water and therefore no longer able to absorb any additional moisture.


Fig.1_Traditional Breather

It is a very simple device based on a great idea, but it has the problem mentioned above, of having to do very rigorous maintenance; something that we all know is complicated, nobody is going to be looking at the transformer every day.

?

Currently, this has been solved with new devices, which are becoming more and more common: Maintenance-free dehydrating breathers that avoid frequent replacement of silica gel by measuring the humidity level of the air in the pipe system and forward the results to control unit.

How do they work ?

In normal operation, the air flowing to the oil expansion vessel is dried by passing it over the silica gel and the moisture content of the air in the pipe to the expansion tank is constantly monitored. When the moisture content reaches the defined limit value, regeneration of the desiccant is activated, depending on the behavior of the operating equipment.

To summarize the main advantages would be:

? Reduces maintenance

? Reduced operating costs and increases operating reliability

? Active protection of the insulation medium against moisture

? Condition dependent and self-learning algorithm

? Easy retrofitting


There are different models of manufacturers on the market, however we must choose the specific model depending on the main parameter such as oil volume, for example we have different types for OLTC, Main Tank Power Transformer up to 40-50 MVA, Main tank PT above 200 MVA, Reactors, etc..

Below figures you can see a model from one of the usual suppliers as MESSKO (MR)

Fig.2_MESSKO MTRAB DB200_MR
Fig.3_Function Description (MESSKO MTRAB_MR)


Finally, one extra advantage of these devices that I find very interesting ?? is that they are known as e-devices, allowing monitoring through an integrated transformer control system. They contribute to optimizing monitoring and would be a necessary part of future digital substations.

?

I share with you some links about interesting videos and information about it.

https://www.youtube.com/watch?v=p34HpY50ckc

https://www.youtube.com/watch?v=EXadRnjrL_8

https://comem.com/en/products/self-dehydrating-breathers-for-smart-transformers-type-esdb/

https://www.reinhausen.com/portfolio/fittings/dehydrating-breather/maintenance-free

I hope you find it interesting


Best wishes and be happy friends

?

?



要查看或添加评论,请登录

Miguel Martínez Pe?as的更多文章

  • E.I.41_Transformadores de Medida II

    E.I.41_Transformadores de Medida II

    Estimados?? Sigamos hablando de los Transformadores de Medida (TTMM), concretamente de los Transformadores de Tensión…

    1 条评论
  • E.I.40_Transformadores de Medida I

    E.I.40_Transformadores de Medida I

    Estimados, buenas tardes Hablemos de los Transformadores de Medida (TTMM), sinceramente estaba reticente a abordar este…

    11 条评论
  • E.I.39_Distancias de aislamiento II

    E.I.39_Distancias de aislamiento II

    ???En primer lugar Feliz 2025 aunque sea con retraso!!! ?? Trataré de escribir este 2025 de una forma más regular, a…

  • E.I.38_Distancias de aislamiento mínimas en aire

    E.I.38_Distancias de aislamiento mínimas en aire

    ???Espero que os encontréis bien!!! ?? Hay algo clave antes de establecer el layout de una subestación como documento…

    1 条评论
  • SPT15_Especificaciones Transformadores II

    SPT15_Especificaciones Transformadores II

    Estimados?? Sigamos comentando aspectos que debemos tener en cuenta en la definición del transformador 1?? Construcción…

  • E.I.37_Reactancias p.a.t. III

    E.I.37_Reactancias p.a.t. III

    Estimados, buenas tardes Tras un paréntesis de unos días, vuelvo a escribir de nuevo; sinceramente no me veía con mucha…

    1 条评论
  • E.I.36_Reactancias puesta a tierra II

    E.I.36_Reactancias puesta a tierra II

    Estimados Sigamos hablando de la reactancia de puesta a tierra. Como comentamos la función principal de la reactancia o…

    8 条评论
  • E.I.35_Reactancias puesta a tierra I

    E.I.35_Reactancias puesta a tierra I

    Estimados ?? Hablemos de la reactancias de puesta a tierra (p.a.

    8 条评论
  • SPT14_Especificaciones Transformadores I

    SPT14_Especificaciones Transformadores I

    Estimados?? Creo que es interesante comentar alguna serie de aspectos a tener en cuenta cuando definimos un…

  • E.I.34_Proceso general desarrollo de una Subestación Eléctrica

    E.I.34_Proceso general desarrollo de una Subestación Eléctrica

    Buenos días a todos Una vez hemos tratado brevemente los principales criterios de dise?o Electromecánicos, antes de…

    3 条评论