Setting of overload, Short circuit & Ground Fault Protection of MCCB (PART-1)
Setting of overload, Short circuit & Ground Fault Protection of MCCB

Setting of overload, Short circuit & Ground Fault Protection of MCCB (PART-1)

Introduction:

  • There are various types of protections setting in MCCB, which define various protection of Electrical Network.
  • In MCCB we can set most of the protection are adjustable according to the Electrical Load profile.
  • The main adjustable Setting in MCCB are
  • Overcurrent Setting
  • Short Circuit Setting
  • Ground Fault Setting

Meaning of each selector switches of MCCB

No alt text provided for this image

Setting of each Protection switch of MCCB

 (1) For Low level Fault / Over Current Protection (Thermal Setting):

  (A) Long-Pickup Current Setting (Ir):

  • It is determines the continuous ampere rating of the breaker.
  • Long time protection is time-dependent.
  • Long Pickup (Ir) value (multiplied by the ampere rating (In) of MCCB) sets the maximum current level which the circuit breaker will carry continuously.
  • If MCB is 1000A Rating but Full Load current is 800A than MCCB Rating can be changed from 1000A to 800A by setting it 0.8, Now Ir=0.8XIn =0.8×1000=800Amp
  • If the current exceeds this value for longer than the circuit breaker will trip at the set delay time.
  • Long time protection is inverse time type (with I2t constant)
  • The long-time pickup (Ir) is adjustable from 4 to 1.0 times the sensor plug rating (In)
  • Standard Practice for Setting:
  • No trip for a current below 105% of Ir
  • Trip in less than two hours for a current equal to for
  • 120% of Ir for an electronic trip unit and for
  • 130% of Ir for a thermal-magnetic trip unit
  • For a higher fault current, the trip time is inversely proportional to the fault current value.

(B) Long-Time delay Setting (tr):

  • Long time delay (tr) sets length of time that the circuit breaker will carry a sustained overload before tripping.
  • The delay bands are labeled in seconds of over current at six times the ampere rating.
  • Long-time delay is an inverse time characteristic in that the tripping time decreases as the current increases.
  • The long-time delay (tr) sets the length of the time that the circuit breaker will carry an over current (below the short-time or instantaneous pickup current level) before tripping.
  • The Long time delay can be set to I2t On and I2t OFF settings.
  • (A) I2t Response:I2t Out ,For coordination with other circuit breakers with electronic trip devices and for coordination with thermal-magnetic circuit breakers.
  • (B) I2t Response: I2t In ,For coordination with fuses and upstream transformer
No alt text provided for this image
No alt text provided for this image

to be continued...

Article Source:https://electricalnotes.wordpress.com/2017/05/09/setting-of-overload-short-circuit-ground-fault-protection-of-mccb-part-1/

Know how iFluids Engineering can save cost in compliance and incident prevention

Electrical Safety

No alt text provided for this image


Lukoz Zachariah K.

Electrical Engineer at Consolidated Contractors International Company

3 å¹´

The article posted from the source https://electricalnotes.wordpress.com/2017/05/09/setting-of-overload-short-circuit-ground-fault-protection-of-mccb-part-1/ is really helpful and thanks for circulating it as it is very useful and handy, also i thank the orginal Author.

赞
回复
Muhammad Asif Malik

Sr. Electrical Engineer | Sr. Electrical Design Engineer | Electrical Consulting Engineer | Audit & Inspection Expert | Electrical Consultant | MIET (UK) |

4 å¹´

Very Informative

赞
回复
Mudasir Shora

Senior Electrical Engineer

5 å¹´

beautifully explained

赞
回复
Concordio (Beboy)_ Tanedo

Assistant Project Manager at Phesco Inc.

5 å¹´

Well explained.?

赞
回复

要查看或添加评论,请登录

John Kingsley的更多文章

社区洞察

其他会员也浏览了