Selection of Epoxy Support Insulators in MV Switchboards

Selection of Epoxy Support Insulators in MV Switchboards

In case of MV Switchboards , it undergoes both electrical and mechanical stress during operation as well as fault conditions. While electrical stress (temperature rise) is the primary criteria for busbar selection, electrodynamic (mechanical) stress influences selection of busbar support insulators.

The support insulators are made from epoxy resin with Brass threaded inserts. Some manufacturers use MS inserts but  Brass is a better option. The insulators have strong electrical and mechanical properties. They also have a very high resistance to chemicals. The following properties are attributed to a good support insulator.

  • -         Good Dielectric Strength
  • -         Sufficient creep age distance.
  • -        Good arcing strength.
  • -         Good bending and tensile strength.
  • -        Compact size

Most of the reputed manufacturers today use insulators complying with the above criteria. The Standards IS 9431, IEC 60273 and IEC 60660 lay down some basic selection criteria for the same. While there are a host of tests that need to be carried out, following tests are paramount :

  • -         Power Frequency Voltage withstand test
  • -         Impulse Voltage withstand test .
  • -        Fall bending load test (Mechanical bending strength) .
  • -        Partial Discharge test
  • -        Water absorption test

The manufacturers complying to the above standards have formulated values corresponding to the above criteria.

In case of any fault, the force on the busbars can be calculated as below :

F = 2 x L/D x Ix Ix 10-4 kN (Where I and I are in kA)

Where I & I are the phase currents, L is the distance between two supports & D is the phase-to-phase distance.

 Let us consider a case of 11kV system with 25kA Short time current capacity . The standard distance between two supports is 500 mm and phase-to-phase distance is 130mm.  In case of three phase symmetrical fault , I= I = Peak withstand current = 62.5kA

 Hence, F = 2 x 500/130 x 62.5 x 62.5 x 10-4 = 3.004 kN

From the figure, we can see that the insulator is subjected to a cantilever force. This can be calculated as,

F= F x [H + (X/2)] /H

Considering 11kV insulator height = 130mm and Busbar width = 80 mm  (For 80x 10mm Busbar)  F = 3.004 x [130 +(80/2)]/130 = 3.92kN

Hence, mechanical strength (Falling Load) for 25kA STC must be at least 4kN .

However, if the same criteria is used for STC= 31.5 kA i.e I=I= Peak withstand current =80kA  with a 100mm x 10 mm busbar ,

F = 4.92kN and F = 6.81 kN

Hence, mechanical strength (Falling Load) for 31.5kA STC must be at least 7.5kN . The same for 40kA STC will be at least 12kN .

Thus , we can understand that in the selection of support insulators, we have to consider the parameters of both creepage as well as mechanical falling load .

要查看或添加评论,请登录

Abhijeet Limaaye的更多文章

  • Substation Automation through IEC 61850

    Substation Automation through IEC 61850

    IEC 61850 is the global protocol for Substation Automation. It can seamlessly integrate multiple functions like…

    3 条评论
  • Smart Grid- For Today and Tomorrow

    Smart Grid- For Today and Tomorrow

    The world we see today is growing more and more power hungry. The Global demand for Energy is expanding at a rate of…

  • HT LBS with Mounting Stand- Reducing Civil Work

    HT LBS with Mounting Stand- Reducing Civil Work

    A manufacturer should always be eager to visit his customers for feedback. In the process of optimizing the production…

  • HT Load Break Switch with Surge Diverter - A customized solution

    HT Load Break Switch with Surge Diverter - A customized solution

    Working with a multitude of customers, I get to understand a lot of practical difficulties. As a manufacturer , I feel…

    3 条评论
  • Conventional ways of Harmonic Mitigation

    Conventional ways of Harmonic Mitigation

    We live in a world today where Electrical equipments are driven by Electronic controllers. Although this has made…

    2 条评论
  • Effect of Voltage Variation on Motors

    Effect of Voltage Variation on Motors

    Three phase Induction motors form the heart of Industrial systems. Thus healthy motors contribute to a healthy industry…

    20 条评论
  • Loose Contacts- The bane of all electrical systems

    Loose Contacts- The bane of all electrical systems

    Loose contact or loose connection is by far the biggest cause of fire hazards and electrical failures . An in-depth…

    2 条评论
  • Selection and Sizing of DG Sets

    Selection and Sizing of DG Sets

    Following is an excerpt from the article by a prominent electrical consultant . Diesel Generator (DG) is used to feed…

    3 条评论
  • LT Distribution Cables for Non-linear Loads - 3.5 Core, 4 Core or 5 Core ?

    LT Distribution Cables for Non-linear Loads - 3.5 Core, 4 Core or 5 Core ?

    This is an excerpt from a article by a veteran electrical consultant . Conventionally we have been using 3.

    4 条评论
  • Tackling Neutral Failure in Banks and Hospitals

    Tackling Neutral Failure in Banks and Hospitals

    This is an excerpt from a discussion with a reputed energy auditor on his experiences in Hospitals and Financial…

    2 条评论

社区洞察