Part Two: A Must-Do for Every School: MERV 13 Filtration Upgrades to Central Air Handling Stations
By Raj Setty, PE, CxA, ASHRAE Epidemic Task Force (ETF)
In the second part of my series, "Clearing the Air for Our Kids: School Ventilation Guidance." I am focusing on another important step school districts and buildings should take as children return to in-person learning: MERV 13 Filtration upgrades to central air handling stations.
The basis for this recommendation is fairly simple. By improving the filtration in air handlers, it’s possible to decrease the chance of aerosolized viral particles being spread through the air distribution system. In simple terms, the goal is to decrease the spread of the particles that carry infectious particles like COVID-19 through the air.
An area of research is focused on the nature of small particles (<10 micron). It’s known that once particles drop below the 5 micron diameter, they tend to stop dropping and instead stay persistent in the air and diffuse throughout the space. Particles in the 5-10 micron range can be transported much longer distances, depending on conditions. The smaller particles (<10 micron) can be inhaled and contribute to the risk of additional infection.
First, some background. While the COVID-19 virus itself is in the 0.125 to 0.3 micron range, the particulate that carry it are likely larger or in the same relative size. While there’s much research going on in this field for COVID-19, we can rely on past research for the Influenza virus. Particles of this size stay suspended in the air and are big enough to carry enough infectious germs that spread infection. The particle mesh of a MERV 13 filter or higher such as HEPA (high efficiency particulate air) will stop most particles above .3 mostly due to Brownian motion. Filters do have a filter efficiency that is dynamic based on mainly airflow and particle sizes. This gives us the indirect correlation of capturing the virus at the filters since we are arresting the particles that carry the viruses.
The viral cells themselves aren’t stable when exposed to air. (Their lipid layer breaks down and the virus is deactivated.) However, when transported inside droplets, the cells present a risk of infection. The ‘larger droplet’ transmission path of viruses and bacteria is widely accepted and considered the base of modern germ theory. In fact, these larger droplets (>10 micron) are the basis of the 6-foot social distancing parameter employed in most public places around the country.
These infectious particles (quanta) are commonly generated through respiration with increased rates while speaking, singing, shouting, or greater cardiovascular activity like running. This risk is recognized by most research and is why ventilation is recommended. From empirical data we know that the risk of transmission outside is much lower than the risk inside and this is likely due to the role of these infectious quanta/aerosolized particles.
The solution to this problem is filtrating the classroom air to remove the viral particles -- but the balance of system considerations, cost, motor capacity, energy offsets and air distribution need to be considered. While higher filtration is more effective, it may not be practical in the central air handling units due to systems limitations and design.
Apply common sense. Install the MERV 13 filters and if there is diminished temperature control or occupant comfort, then go back to the next filter size such MERV 12. HVAC systems are sized for peak conditions and will have capacity at part load conditions. Occupants should be told that due to the higher grade of filters, during the peak heating and cooling days they may experience space temperatures, over 74 F summer and under 68 F Winter. If it continues to be a problem, go back to the rated filter size of the HVAC unit.
Additionally, existing equipment has several limitations such as fan static capacity. Higher levels of filtration are better, but from research, it has been determined that MERV 13 to MERV 14 is where diminishing returns begin in the effectiveness of these particles being removed. There is a filtration efficiency that is gained with multiple passes across the filters every air. We want to achieve a CADR (clean air delivery rate) of 4-6 ACHR. Filter the air and dilute with fresh air every 10-15 minutes.
For those who don’t know, MERV stands for Minimum Efficiency Reporting Value. It’s a system used to evaluate the efficiency of an air filter and is used to report a filter's ability to capture larger particles between 0.3 and 10 microns (μm). This value is helpful in comparing the performance of different filters. In simple terms, the higher the MERV rating (such as MERV 8 or MERV 13), the higher the air filtration. Note that MERV ratings are not additive and a MERV 6 plus a MERV 8 does not give you a MERV 14 rating.
See Kowalski and Bahnfleth article circa 2002.
It’s widely believed that MERV 13 is likely the highest filtration level that most existing systems can accommodate and is why it’s recommended as a minimum across the industry. An increase from MERV 8 or MERV 11 represents a substantial increase in the efficacy of filtration of small infectious particles.
If MERV 13 filters can’t be installed in your school, consider the following:
- Increase the filtration in the unit to the maximum available - check the fan static at maximum cfm. Fans have a system curve of pressure vs. cfm. Find your spot on the curve.
- Install a recirculation fan filtration unit and duct into the return of units
- Provide a HEPA air cleaner filtration unit in each classroom which re-circulates air within the space - simplest and highly effective. This can be portable or fixed in the ceilings. Great place to install air cleaners are in bathrooms where you can not socially distance.
- Consider additional treatment technology such as UV-C to stop the replication of airborne infectious aerosols
- Refer to ASHRAE Filtration and Disinfection recommendations
- Consider alternate filter locations in return duct or grille but consider static pressure drop implications and relationship with outside air dampers
- Insist that you designers/TAB agents check the existing filter clean and dirty differential pressure and find a retrofit MERV 13 filter that matches the clean filter differential pressure reading. The changing of the filter should have a minimal impact on the air handler fan performance.
One of the most important things a school can do to make the learning environment safer for children is upgrading the building’s central air handling station to MERV 13. For more specific instructions or to learn how to do a filtration analysis, contact me directly on LinkedIn.
Buildings Energy Efficiency and Smart Building Technology Professional
3 å¹´Thank you for sharing Raj
Duct & Vent Cleaning of America, Inc, President
3 å¹´Very good suggestion to make! There are some very important things to plan and consider before the upgrade. Ensure the equipment can handle the added load. Ensuring the coils, other components and ductwork are clean to be certain that the filters do not load to quickly after install. Otherwise you may find yourselves needing more funding for equipment changeouts and maintenance.
Raj, thank you for sharing great content. Please keep educating everyone on this matter so we can all make the world safer, healthier, and more productive.
Director of Overseas Business Operations at SETTY
3 å¹´Well said
Executive Director, Maintenance and Operations at San Marcos Unified School District
3 å¹´We have used MERV 13 since August with 1/2 of the students (load) in the classrooms...this week we returned to 100% of the students back in the classrooms. To this point we have not experienced an increase in mechanical failures due to increased filtration, but we will be putting that to the test this week as weather warms up in South Orange County Thursday and Friday. School is out June 3rd, we hope to make a case for MERV 13 going forward if they can hold up for 6 more weeks.