An overkill of solar installation. Wasted capital investment. Poor planning and study of requirement.
WAVEFORMS

An overkill of solar installation. Wasted capital investment. Poor planning and study of requirement.

We had the opportunity of studying and analyzing the issues of power quality in one of the railways division. The installation reflects how resources are wasted due to improper planning and power study prior it Installation of this 900KW solar installation.

Some of the serious issues faced by the railways are the following:

1.?????? Excess and a overkill of solar generation 900 KW when the total load is only 280KW.

2.?????? No facility for export of solar energy or storage.

3.?????? High Harmonics generated max 99%, especially when there is clouding, consequently heating of transformers due to harmonics (Power quality and RF range)

4.?????? Power factor oscillation from leading PF pf -0.36 to lagging 1.

5.?????? APFC not in working condition and Hence manually operated. Which can cause harmonic resonance, which could harm the electrical system and all equipments connected to it.

6.?????? No Harmonics Mitigation technique implemented prior to adding solar.

7.?????? The string Inverters shut down when there is excess generation. Precious energy wasted

We are reproducing some of the data recorded for the readers, to create awareness how design power study and power quality planning? is critical for Distributed energy resources Installation (DER) for successful installation of solar Plants.

RMS CURRENT:

RMS CURRENT

VARIATION OF POWER FACTOR AT SOLAR WORKING CONDITION:

INCREASE OF HARMONICS WHEN INTERMITTENT CLOUDING & SOLAR INJECTION:

TOTAL HARMONICS DISTORTION
INDIVIDUAL HARMONICS DISTORTION


VIDEO LINK:

https://www.youtube.com/shorts/hwi-F26aTHE?feature=share


FOLLOW US WAVEFORMS
[email protected]

OUR RANGE OF PRODUCTS:


  1. WAVEFORMS TERMINATOR - ADVANCE PASSIVE HARMONICS FILTER.
  2. WAVEFORMS HYBRID HMT - HARMONICS MITIGATION TRANSFORMER.
  3. WAVEFORMS SINEWAVE FILTER - SINE FILTER FOR OUTPUT SIDE OF VFD.
  4. WAVEFORMS TRIPLEN ELIMINATOR - FOR 3RD,9TH, 15TH..... HARMONICS (Neutral Harmonics Eliminator)
  5. SOCOMEC UPS.
  6. CVT, STABILIZER, LED LIGHTING & INVERTER.


Ian C Evans

Principal Electrical Engineer at Harmonic Solutions Oil & Gas

2 个月

John, same as wind. Caused by dash for cash !

回复
Modi P

Business Head-Asia & M.E. @ A. Eberle

2 个月

John Simon what is meant by point 7. Do inverter trip (because of - over voltage or under voltage) or something else

回复

要查看或添加评论,请登录

社区洞察

其他会员也浏览了