Out of Control? A Look at Hazardous Chemicals and Control Areas

Out of Control? A Look at Hazardous Chemicals and Control Areas

No alt text provided for this image

Many chemicals used for cleaning and sanitizing food and beverage facilities are corrosive or toxic in nature and are classified as hazardous materials. (See definitions in “Experience in Brief.”) The use and storage of these chemicals is regulated by current building and fire codes. These codes identify the maximum quantity allowed to be stored and also how these hazardous substances may be stored within a facility.

Health hazard chemicals must be stored within designated areas of a facility called control areas. These are spaces within a building that are enclosed and bounded by exterior walls and/or fire-rated construction, where hazardous materials not exceeding the maximum allowable quantities are stored. The overall size of a control area is not limited: An entire facility can be considered one control area if the allowable quantities for one control area are not exceeded; however, the maximum number of control areas permitted in a typical one-story facility is four. Where multiple control areas are used, they are required to be separated from each other by no less than a one-hour fire barrier.

The 2021 International Building Code allows up to 1000 gallons of corrosives and 100 gallons of toxic chemical within a control area. These quantities are assumed to be located within a facility that is equipped throughout with an automatic sprinkler system. Allowable quantities will decrease within a facility that is not fully sprinkled, but can be doubled if stored in approved storage cabinets.

No alt text provided for this image

If the maximum storage quantities are exceeded within an individual room, area, or building defined as a single control area, the area designated for health hazard chemical storage no longer meets the defined limitations of a control area. In this case, it is required to be classified as a hazardous occupancy (H-4). An H-4 hazardous classification affects many aspects of the building design, including fire separation, personnel egress, and spill control and containment. These spaces require a fire barrier that can range from one- to four-hour and include a reduction in maximum egress travel distance and the installation of panic exit device door hardware. In addition, hazardous occupancies require spill control to eliminate the spread of liquid to adjacent areas, secondary containment sized to hold the largest vessel plus 20 minutes of fire sprinkler flow, and continuous ventilation and stand-by power as life safety components. Proper storage of hazardous chemicals is a complex issue. Consult with a qualified architecture and engineering firm to determine how to best keep your facility in compliance.

Want to read more Hixson From Experience articles? Subscribe on LinkedIn or discover one or more of our other newsletters here!