The neutral conductor sizing and protection
Yusof Kushki
Senior Electrical Engineer at EIED (OIEC Group), EPC Project Engineer at Oil & Gas & Petrochemical & DRI & Steel Plants
The neutral conductor
The cross section area (c.s.a.) and the protection of the neutral conductor, apart from its current-carrying requirement, depend on several factors, namely:
The color of the neutral conductor is statutorily blue. PEN conductor, when insulated, shall be marked by one of the following methods:
Sizing the neutral conductor
Influence of the type of earthing system
TT and TN-S schemes
TN-C scheme
The same conditions apply in theory as those mentioned above, but in practice, the neutral conductor must not be open-circuited under any circumstances since it constitutes a PE as well as a neutral conductor
Minimum cross section area of protective conductors
the above table is based on IEC 60364-5-54. This table provides two methods of determining the appropriate c.s.a. for both PE or PEN conductors.
IT scheme
In general, it is not recommended to distribute the neutral conductor, i.e. a 3-phase 3-wire scheme is preferred. When a 3-phase 4-wire installation is necessary, however, the conditions described above for TT and TN-S schemes are applicable.
Influence of harmonic currents
Effects of triplen harmonics
Harmonics are generated by the non-linear loads of the installation (computers, fluorescent lighting, rectifiers, power electronic choppers) and can produce high currents in the Neutral. In particular triplen harmonics of the three Phases have a tendency to cumulate in the Neutral as:
shows the load factor of the neutral conductor as a function of the percentage of 3rd harmonic.
In practice, this maximum load factor cannot exceed 1.732
Load factor of the neutral conductor vs the percentage of 3rd harmonic
Reduction factors for harmonic currents in four-core and five-core cables with four cores carrying current
The basic calculation of a cable concerns only cables with three loaded conductors i.e there is no current in the neutral conductor. Because of the third harmonic current, there is a current in the neutral. As a result, this neutral current creates an hot environment for the 3 phase conductors and for this reason, a reduction factor for phase conductors is necessary (see Figure below).
Reduction factors for harmonic currents in four-core and five-core cables (according to IEC 60364-5-52)
If the neutral current is more than 135?% of the phase current and the cable size is selected on the basis of the neutral current then the three phase conductors will not be fully loaded. The reduction in heat generated by the phase conductors offsets the heat generated by the neutral conductor to the extent that it is not necessary to apply any reduction factor to the current carrying capacity for three loaded conductors.
领英推荐
Reduction factors, applied to the current-carrying capacity of a cable with three loaded conductors, give the current-carrying capacity of a cable with four loaded conductors, where the current in the fourth conductor is due to harmonics. The reduction factors also take the heating effect of the harmonic current in the phase conductors into account.
Examples
Consider a three-phase circuit with a design load of 37 A to be installed using four-core PVC insulated cable clipped to a wall, a 6 mm2 cable with copper conductors has a current-carrying capacity of 40 A and hence is suitable if harmonics are not present in the circuit.
For this load a 10 mm2 cable is necessary.
In this case, the use of a special protective device (Compact NSX equipped with the OSN trip unit for instance) would allow the use of a 6 mm2 cable for the phases and of 10 mm2 for the neutral.
For this load a 10 mm2 cable is suitable.
In this case, the use of a special protective device (Compact NSX equipped with the OSN trip for instance) would allow the use of a 6 mm2 cable for the phases and of 10mm2 for the neutral.
Protection of the neutral conductor
Protection against overload
If the neutral conductor is correctly sized (including harmonics), no specific protection of the neutral conductor is required because it is protected by the phase protection.
However, in practice, if the c.s.a. of the neutral conductor is lower than the phase c.s.a, a neutral overload protection must be installed.
Protection against short-circuit
If the c.s.a. of the neutral conductor is lower than the c.s.a. of the phase conductor, the neutral conductor must be protected against short-circuit.
If the c.s.a. of the neutral conductor is equal or greater than the c.s.a. of the phase conductor, no specific protection of the neutral conductor is required because it is protected by the phase protection.
Breaking of the neutral conductor
The need to break or not the neutral conductor is related to the protection against indirect contact (fault protection).
In TN-C scheme
The neutral conductor must not be open-circuited under any circumstances since it constitutes a PE as well as a neutral conductor.
In TT, TN-S and IT schemes
In the event of a fault, the circuit-breaker will open all poles, including the neutral pole, i.e. the circuit-breaker is omnipolar.
The action can only be achieved with fuses in an indirect way, in which the operation of one or more fuses triggers a mechanical trip-out of all poles of an associated series-connected load-break switch.
Notes
In some coutries the rules applied for TN-S are the same as the rules for TN-C
Reference: Schneider electric electrical installation guide.
candidat à la profession d’ingénieur (CPI) en Génie électrique Power system Specialist -Data Centers and Power Plants
2 年???? ??? ?????
Senior Electrical Engineer at EIED (OIEC Group), EPC Project Engineer at Oil & Gas & Petrochemical & DRI & Steel Plants
2 年#yu_ku