Maximizing Solar Safety: Essential Precautions for PV Systems
Harnessing solar energy isn't magic—it’s science, precision, and strict safety protocols.?
As utility-scale solar installations evolve with advanced?PV modules, inverters, battery storage, and metering systems, safety challenges grow. Unlike conventional power sources, PV systems generate?unregulated "wild" currents, requiring unique safety measures and specialised tools to mitigate risks.?
Understanding the?top three electrical hazards?in PV systems is essential to protecting both workers and infrastructure. Here’s what you need to know to enhance?solar safety and system reliability.?
1. Shock or electrocution from energised conductors?
Like other electric power generation, PV systems present the risk of shock and electrocution when current takes an unintended path through the human body. Current as low as 75 milliamps (mA) across the heart is lethal. The human body has a resistance of about 600 ohms. Per?Ohm’s law, voltage (V) equals current (I) times resistance (R), so V = IR.?
To calculate the amount of current that would course through a person’s body if exposed to 120 V, simply divide 120 V by 600 ohms (I = V/R), which totals 0.2 amps or 200 mA. That’s more than 2.5 times the lethal limit of 75 mA, so protecting yourself and your workers against such an event is critical.?
Electrical shocks are typically caused by a short circuit resulting from corroded cables and connections, loose wiring, and improper grounding. Key places to look for these conditions in a PV system include the combiner box, PV source and output circuit conductors, and the equipment grounding conductor. The grounding conductor bonds all metallic components together—and eventually to the ground—through the grounding electrode conductor and grounding electrode.?
Control measures: Rapid shutdown systems?
The energy produced from PV string systems varies directly with the sun. To reduce shock hazards for technicians and first responders, we need a way to shut those strings off during a short circuit or power outage. The 2017 National Electric Code (NEC) Section 690.12 requires the “rapid shutdown” of PV systems inside and outside the PV array boundary. According to section 690.2 of that code, a PV array boundary is a mechanically integrated assembly of modules or panels with a support structure and foundation, tracker, and other components that form a DC or AC-producing unit. This includes controlled conductors located inside the boundary or up to three feet from the point where they penetrate the surface of the building.?
As of 2019, the NEC made these requirements more stringent by requiring:?
Rapid shutdown devices must be located either at the service disconnect or at a special rapid shutdown switch. An exception exists for systems controlled by module-level power electronics—such as micro-inverters and power optimisers—that reduce voltage. Arrays with no exposed conductive parts and located more than eight feet from exposed grounded conductive parts are not required to comply.?
In addition, many jurisdictions in the U.S. require rooftop PV arrays to have setbacks that prevent firefighters from accessing the system. For instance, the California Residential Fire Code requires PV modules to be at least three feet from the roof’s ridge.?
2. Arc faults that spark fires?
As with any electrical system, fire is always a potential hazard. Perhaps one of the most common causes is electrical arc faults, which are high-power discharges of electricity between two or more conductors. The heat caused by this discharge can deteriorate the wire insulation, causing a spark or “arc” that causes a fire.?
PV systems are subject to both series arc faults caused by a disruption in the continuity of a conductor or parallel arc faults caused by unintended current between two conductors, often due to a ground fault.?
Control measures: Arc-fault circuit interrupters?
An arc fault may lead to a short circuit or ground fault, but it may not be strong enough to trigger a circuit breaker or a?ground fault circuit interrupter?(GFCI). To protect against arc faults, you need to install an arc-fault circuit interrupter (AFCI) outlet or an AFCI circuit breaker. AFCIs detect low-level hazardous arcing currents and shut off the circuit or outlet to reduce the chances of such an arc fault sparking an electrical fire.?
NEC Section 690.11 mandates that PV systems operating at 80 V DC or greater between any two conductors be protected by a listed PV AFCI or equivalent system component. The protection system must be able to detect arc faults resulting from a failure in the intended continuity of a conductor, connection module, or other component in the PV system’s DC circuits.?
3. Arc flash leading to explosions?
Large-scale PV arrays with medium and high voltage levels are susceptible to arc flash. This is especially true when a technician checks for faults in energised combiner boxes where PV source circuits are combined in parallel to increase current and when checking medium-to-high voltage switchgear and transformers. An arc flash releases hot gases and concentrated radiant energy up to four times the temperature of the sun’s surface—as high as 35,000° F (~19,500° C). It occurs when a large amount of energy is available to an arc fault in both DC and AC conductors.?
Arc flash is an issue for systems over 400 V, so residential inverters typically have a maximum input voltage of 500 V and large-scale inverters with a maximum of 1,500 V are at risk. Before the advent of large-scale solar energy systems, arc flash was solely considered an AC issue since DC voltage was limited to off-grid applications with less than 100 V batteries. The National Fire Protection Association?(NFPA) Standard 70E requires an arc flash hazard risk analysis to be conducted and Personal Protective Equipment (PPE) used for DC systems over 100 V.?
Control measures: AC and DC side mitigation?
Arc flash mitigation in PV systems is divided into DC (before the inverter) and AC (after the inverter). DC-side mitigation for large solar arrays (100 kW +) is significant at the combiner box, where multiple strings of solar panels are combined in parallel to increase the current. To reduce the potential for arc flash, large-scale systems can use multiple string inverters that connect multiple strings in parallel instead of using one or two large central inverters that require combiner boxes. AC-side mitigation includes arc-resistant switchgear, which redirects arc flash energy through the top of the enclosure, away from personnel and equipment.?
Choose the correct solar testing equipment.?
Protecting your workers and your PV system from electrical hazards requires adherence to safe work practices and ensuring that your equipment is rated to withstand these potential hazards.? That means multimeters, test leads, and fuses must all be rated for the application you are working on. Here are some basic guidelines:?
These are just the highlights of how to work more safely with PV systems. When testing or servicing electrical equipment, be sure to follow all relevant safety standards and regulations, manufacturer’s instructions, and your company’s safety procedures.?
About the expert?
Michael Ginsberg is a solar expert, trainer for the U.S. Department of State, author and Doctor of Engineering Science candidate at Columbia University. He is also chief executive officer of Mastering Green,?where he has trained nearly a thousand technicians worldwide in solar PV installation, maintenance, and operation.?
?