LV Motor Protection - LS"I" Recommendations
Shailesh Chetty
Electrification Technology Solution & Integration @ Shell | Digital Transformation
Instantaneous Release setting recommendations:
Instantaneous Release setting in the MCCB is set to a value higher than the highest anticipated magnetizing inrush current, while switching-on the motor.
Lets Have a Generalized approach to evaluate best setting,
Staring Current (Ist)
Motor rated current (IrM)
Tolerance on Starting current:
Ratio Ist/IrM is normally allowed to be 20 % higher than the rated value given by the manufacturer, this needs to be checked in datasheet furnished by manufacturer (The ratio Ist/IrM takes care of the saturation of the reactances of asynchronous motors).
Hence,
Maximum anticipated starting current: = 1.2 x Ist
Transient inrush current (peak): = √2 x 1.2 Ist = 1.697 x Ist
As per IEC 60947-2, there is a tolerance of +/- 20% in the values of current for tripping of the circuit breaker by short-circuit releases.
Hence,
Effective setting of the instantaneous release setting in the MCCB should be above this tolerance band
Suggesting Setting: 1.697 / 0.8 = 2.1213 Ist (peak value)
We should note that Instantaneous setting in the MCCB is in RMS value
Hence,
Suggesting Setting: 2.1213 / √2 = 1.5 Ist
Thus, the instantaneous setting in the MCCB has to be above 1.5 Ist
i.e; if Ist/IrM = 6 then Instantaneous stage setting should be set ≥ 9 x IrM
Reference: Paper by KSK on MCCB for LV Motor feeders
Independent Consultant at Garden Power Technologies Pvt Ltd
8 年With a setting of 9X IrM, when would this protection operate? Would it be better for a lower setting that comes into operation only after the motor starts?
Senior MEP Engineer
9 年what happens if we put over rated MPCB for motor/ motor rating is 7.5KW mpcb rating is 17-22Amps. waiting for your solution
Thank you so much for this article.In your reference you mentioned KSK,what does that stand for?
Lead Electrical Commissioning Engineer | FPSO RAIA | Pre-Operations | Start-up | Engineering
9 年Mr.Shailesh is dedicated electrical engineer. ...Great Job
Project Manager. The Commonwealth of Independent States Project PV Solar power plants in Uzbekistan.
9 年Thank your for article ! Best regards !