How to Selection of kA-Short Circuit Breaking Current rating for 400kVA Transformers 11000V/415V Medium Voltage VCB Panel Board?
L&T

How to Selection of kA-Short Circuit Breaking Current rating for 400kVA Transformers 11000V/415V Medium Voltage VCB Panel Board?

How to Selection of kA-Short Circuit Breaking Current rating for 400kVA Transformers 11000V/415V Medium Voltage VCB Panel Board?

a) Power Grid Source Side Fault????????: 350MVA * Consider **

b) Nominal voltage, Un (kV) ???????????????: 12kV????????** Un = 3.6/ 7.2/12/17.5/ 24/36 kV*

c) 400kVA Transformer Primary Current=19Amp

d ) Calculation of Source Impedance (Zo):?

No alt text provided for this image
No alt text provided for this image

e) Short Circuit Breaking Capacity of Breaker. Isc (kA)

No alt text provided for this image
No alt text provided for this image

So We Selecting 630Amp, 26.3kA Breaking capacity Medium Voltage Switchgear. Refer Below Datasheet of Medium Voltage Breaker.

No alt text provided for this image

GA Drawing of Outdoor Duty MV Panel.

No alt text provided for this image

Foundation Drawing.

No alt text provided for this image