Fault Level and Fault Current

Fault Level and Fault Current

Fault level at any given point of the Electric Power Supply Network is the maximum current that would flow in case of a short circuit fault?.

Formula to Calculate Fault Level -

Fault MVA = (Transformer Rated MVA x 100) / Percentage Impedance

Fault Current = (Fault MVA) / ( 1.732 x Voltage in KV)

Please note that here Secondary Voltage will be considered in fault current formula due to fault will take place in secondary side.

Example= Suppose We have transformer which is rated at 25 MVA , percentage impedance is 11.9 , Primary and secondary voltage is 132 KV and 11 KV respectiely , fault MVA will be-

Fault MVA = (25 x 100) / 11.9

= 210 MVA ( This is maximum MVA during short circuit fault)

Now During fault maximum current -

Fault Current = (210) / ( 1.732 x 11 )

= 11 KA ( approximately )

Fault level for above transformer will be 210 MVA and 11 KA .

Note that Time is also considered to withstand with fault level.

HT switchgears are rated for 3 seconds and LT are rated for 1 seconds.


Laxman Chaudhary

Senior Section Engineer Electrical at JKCement | Ex-UltraTech Cement , Heidelberg Cement India , Shree Cement | Electrical Graduate with Honors | 8 Years of Experience in Cement Plant Project, Operation & Maintenance

1 个月

Percentage impedance (%Z) varies with transformer rating. It is not a fixed value across all transformers. The main factors affecting %Z include: 1. Transformer Rating (MVA): As the transformer's MVA rating increases, the percentage impedance typically increases to limit fault currents. 2. Voltage Level: Higher voltage transformers tend to have higher %Z to control short-circuit currents. 3. Design & Construction: The winding configuration, core design, and cooling method also influence %Z. 4. Application Requirement: Power system stability and fault current considerations affect the choice of %Z for different applications (e.g., generator transformers, distribution transformers). For example: A small distribution transformer (e.g., 500 kVA, 11 kV) may have %Z around 4–6%. A large power transformer (e.g., 100 MVA, 220 kV) may have %Z in the range of 10–15%. So, percentage impedance is varied with transformer rating rather than being fixed.

回复

Has the percentage impedance been varied with Transformer rating or kept fix(assumed) for voltage level

回复

要查看或添加评论,请登录

Laxman Chaudhary的更多文章

社区洞察

其他会员也浏览了