An Evening with Motor Driven Reel Conductix Wampfler Trouble Shooting:

An Evening with Motor Driven Reel Conductix Wampfler Trouble Shooting:


Trouble shooting is in the blood. We have a Transfer Cart, it is one the section of our plant as the name suggest it usually takes concrete products on steel board which are coming from Concrete Block Making Machine and transfer to the curing chambers. As usual on Monday we turned our plant on and started to check each and everything either up to the mark or not. We received a bundle of complains that transfer cart is not working appropriately such as earth fault came in SEW Euro drive, MCBs tripping and sometime fluttering of contactors etc. we started to check the volts phase to phase and phase to neutral and found it normal. Usually faults were coming when Transfer cart was moving where as in stationary position there were no faults.

Initially I thought contactor had been out of order because rest of faults were not coming to frequently, there was interlocking between contactors so I replaced one of it and take the transfer cart under observation. There was not any sort of improvement. Faults kept coming in a same fashion. I decided to check Harting plug whose cable was coming from Conductix Wampfler motor driven cable reel. Sooner we detach the harting coupler we saw cable’s cores were in bad condition, core’s insulation has come out as it felt bare cores were kissing each other. I also open the cover of slip ring I found same pathetic condition of cable’s core, I even saw ground cable was broken by the way it was 18 core 2.5mm2 cable.

Obliviously, we had Conductix Wampfler Motor Driven Cable Reel in spare so we decided to replace it and as well as Harting Coupler. All faults had been vanished after replacing the both items Transfer Cart started to work smoothly. Trouble shooting is something which gives us energy if I got success to removing faults and in case if you are not succeed, we should not give in at least keep working and working then success will come to your feet. The reason behind this article: firstly is to share my experiences with all you so anyone can take advantages behalf of my experiences and secondly I want to improve my writing skills too. Hope you all would like it. Waiting for your positive gesture.

Motor Driven Cable Reel



Jamil Ashraf

ELECTRICAL & AUTOMATION ENGINEER

5 年

I am not aware about that?

回复
Arsalan .

SENIOR ENGINEER (ATM)

5 年

Sir , Magnacrete is going to established new plant at Sukkur , any update ??

回复
Asif Iqbal

Assistant Manager | Ports & Terminal | Asset Management | Electrical Maintenance & Reliability

5 年

Good effort #jamil

回复

要查看或添加评论,请登录

Jamil Ashraf的更多文章

  • Industrial Electrical Shortcomings:

    Industrial Electrical Shortcomings:

    Need to Thing Out of The Box. Sometimes, you have to think out of the box otherwise you will keep moving in a circle as…

    2 条评论
  • What the Warehouse In-Charge Told me

    What the Warehouse In-Charge Told me

    The reward is the best medicine for human beings that's why we put a lot of effort into any work. Once I went to the…

    3 条评论
  • Industrial Electrical Shortcomings:

    Industrial Electrical Shortcomings:

    The motor's winding lead wire got damaged: I received a complaint yesterday evening that one of the motors was not…

  • Industrial Electrical Shortcomings:

    Industrial Electrical Shortcomings:

    The AC motor Issue Last week, we had an amazing fault so I thought why should not I write an article on it? Here you…

    13 条评论
  • If he called me, would not I support him?

    If he called me, would not I support him?

    Life is not as simple as it seems. Life is a long journey with highs and lows.

    2 条评论
  • Industrial Electrical Shortcomings

    Industrial Electrical Shortcomings

    Does mindset matter for troubleshooting In my opinion, the mindset does matter for troubleshooting. How do you take the…

    7 条评论
  • Industrial Electrical Shortcomings:

    Industrial Electrical Shortcomings:

    The Ethics Of Troubleshooting This line comes to your mind from time to time from where to start troubleshooting. If…

    1 条评论
  • Industrial Electrical Shortcomings:

    Industrial Electrical Shortcomings:

    Mother Of All Hidden Faults As I always say the mother of all hidden faults is the Profibus fault. This is not just a…

    1 条评论
  • Industrial Electrical Shortcomings:

    Industrial Electrical Shortcomings:

    Safety Does Matter It was a maintenance day at my factory. We usually do maintenance every Sunday.

    1 条评论
  • Industrial Electrical Shortcomings

    Industrial Electrical Shortcomings

    The SEW Euro Drives During the major overhauling of our plant last week, I decided to do service and maintenance of all…

    6 条评论

社区洞察

其他会员也浏览了