Energy consumption of industrial-size refrigeration systems
Danfoss Climate Solutions
We engineer energy-efficient heating and cooling solutions to help the world get more out of less
In this study, based on the original work by Thomas Lund , Morten Juel Skovrup , and Mads Holst , we are analyzing and comparing the energy consumption of common industrial size systems:
The study includes different variations in system design and ambient conditions, with each system tested in four different sizes, using both a ‘standard’ and an ‘optimized’ approach. The comparison is based on simulation models, including real compressor data, complex heat exchanger models, and real ambient data.
These optimizations include parallel compression, hybrid coolers, ejectors, and economizers where applicable. Additionally, we have conducted calculations across various climate conditions, ranging from cold to hot climates.
Since the comparison results depend on the inputs to the simulation software, this study offers an overview of how the choices made in the simulation software impact the overall results
1. Introduction to data collection methods
Much has already been said when it comes to industrial refrigeration and the various systems available. Here, data is key, and with the figures below, our aim is to provide reliable data that can translate to qualified business decisions.
However, while it is essential to compare operating data from actual systems in operation, it is important to note that data collected in this manner is susceptible to various factors that can make it less reliable.
These influencing factors include operational variations, the allocation of low-temperature (LT) and medium-temperature (MT) loads, ambient conditions, as well as the design, construction, and maintenance of the systems.
Simulation software (specifically, Pack Calculation Pro ver 4.20 by IPU) was used to collect the data to reflect a real-world environment to mitigate these factors. This includes compressor efficiencies, ambient data, complex condenser/gas cooler models, and control strategies, which are used to paint a more robust picture of the difference between system types under uniform conditions and constraints, ensuring equitable consideration of their advantages and disadvantages
2. Calculation parameters
All five systems are calculated in both a ‘standard’ and an ‘optimized’ configuration.
Types of systems explored:
Transcritical configurations
When it comes to transcritical systems, the ‘standard’ configuration entails that the system is equipped with a simple booster unit, as this was the system originally quoted by the supplier. On the other hand, the ‘optimized’ systems incorporate hybrid (adiabatic) gas coolers, parallel compression (DX only), and gas ejectors.
The remaining system types
For the remaining systems, the distinction between ‘standard’ and ‘optimized’ configurations is primarily related to the utilization of economizers and a reduced temperature difference in the cascade cooler.
While some might assume that the optimization process would involve reduced temperature differences in air coolers and condensers/gas coolers, we have gone in a different direction, as this alteration can be done across all system types with minimal impact. Instead, we opted to size heat exchangers uniformly.
Temperature range and region
To accurately reflect real-world scenarios, ambient condition data collected from Oslo, Frankfurt, and Rome are used, providing us with insights into performance throughout a range of colder and warmer climates.
Cooling loads–the common denominator
To ensure consistency, the duty delivered across all systems is the same and split into a low temperature (LT) and a medium temperature (MT) load.
LT cooling load delivered at an air temperature of -2°C MT cooling load delivered at an air temperature of -25°C
In the bulk of the calculations, the MT cooling load is three times that of the LT cooling load. However, the measures of the reverse split, e.g., LT cooling load = 3 MT cooling loads, have been performed in a few of the cases to highlight the significance of the LT/MT split.
Initially, the system types are calculated in 4 different sizes, with LT/MT cooling loads at:
While the simulation software allows for variable cooling load simulations, we have set a constant cooling load to avoid obscuring the inherent behavior of the refrigeration system, which can occur when introducing any functionality dependent on time and/or ambient temperatures.
Variable load profile
Typically, two distinct mechanisms are employed to create a variable load profile: changes in ambient temperature and production cycles. In many production cycles, full production occurs during the day, with reduced activity at night. Consequently, whether driven by ambient temperature or production cycles, the system's capacity is decreased during colder periods of the day or year.
Maintaining a constant capacity results in the refrigeration systems operating more frequently during colder periods. Here, transcritical R744 systems shine as their efficiency loss at high temperatures is greater compared to other systems.
With the room air temperatures fixed at -2°C and -25°C for MT and LT, the evaporating temperatures have been derived from the following assumptions:
Condensers and gas coolers
Condensers/gas coolers were sized according to the following:
Compressor selection
Compressors for the transcritical systems were selected by a supplier and are commercially available from major manufacturers. The simulation software provided the performance correlations for R744 compressors, initially sourced from a supplier's software. For the R717, R507, and R744 compressors in the cascade system, their performance data was obtained from supplier calculation programs and integrated into the simulation software.
Considering heat recovery
Finally, heat recovery has been left out of this study. The simulation program primarily focuses on system control to deliver the desired cooling capacity. Incorporating heat recovery could result in a suboptimal refrigeration cycle, hindering any economic benefits.
In addition, the varying constraints on heat recovery systems, including temperature ranges and required capacities, differ significantly among different installations. Accounting for these variations would introduce many complexities that could obscure the results rather than enhance clarity.
3. Standard system calculations
Initially, calculations encompassed all system sizes and types in all locations, yielding a substantial volume of data. The primary metric is the annual power usage, measured in MWh, and serves as the core result, as seen in Table 3. Additionally, the associated CO values are presented in Table 4.
领英推荐
Key observations
At first glance, these COP reveal several trends. For one, the COP in transcritical systems remains relatively constant across different sizes, except 50/150kW. This variation could be attributed to an unfortunate compressor type selection made by the supplier, making the three larger sizes the only representative examples in the transcritical category.
As for the remaining systems, there is a slight upward trend in COP as system size increases, although not substantial. Consequently, the focus was shifted onto the 300/900kW system exclusively to reduce the workload and improve clarity.
Another observation is that in all situations, the two-stage R717 system delivers the best COP. However, a few points merit consideration regarding this result.
The LT room temperature of -25°C results in evaporating temperatures of -33°C in the R744/R717 cascade system. This is only on the fringe of where a cascade system starts to become competitive compared to a two-stage R717 system. As the evaporating temperature decreases, for instance, with more heavy-duty freezing applications, the cascade system eventually surpasses the efficiency of a two-stage R717 system.
Regarding the R507 system, it is included primarily for reference, but it closely trails the two-stage R717 and cascade system in terms of efficiency, although slightly behind.
Nevertheless, as the main focus is energy efficiency, it is more sensible to look at the annual COP average, using the total delivered cooling effect from the individual system sizes.
Power consumption
When examining Table 5, the 300/900kW systems in colder climates, e.g., Oslo, the transcritical systems come close to the efficiency of the two-stage R717, with the flooded version being 9% higher in power consumption and the DX version approximately 17% higher.
However, in warmer climates, e.g., Rome, the transcritical systems exhibit far higher power consumption at 32% and 45%. Clearly, the transcritical systems face challenges in warmer climates, which is to be expected. When comparing them to Oslo as the reference point, it becomes evident how these systems respond to changes in ambient temperature.
The influence of load profile
As previously mentioned, the load profile was a constant in these calculations. And looking at the relative power consumption compared to two-stage R717 in Table 7, two-stage R717 was again the most efficient.
Nevertheless, a sample load profile was used within the simulation program to provide further insight into how the load profile impacts the results. Load profiles can have a variety of forms, but in this sample, the cooling load was adjusted to vary from our baseline capacity at maximum dry bulb temperature at the given location down to 35% of this at a temperature equivalent to the room temperature. The variation measured was linear, and the delivered cooling effect remained constant across system types but varied with location.
Generally, the transcritical systems benefitted in the region of 5 to 10% from the constant load profile, although this depends on the actual configuration of the load profile. The individual systems’ response to colder climates (Oslo) was slightly better than warmer climates (Rome), with 4 to 5% lower energy consumption with the constant load profile.
LT and MT loads explored
Finally, the split between LT and MT load was examined using the initial constant load profile. The recalculation of the 300/900kW system to 900/300kW provided the following power consumption in MWh, as demonstrated in Table 8.
Again, as shown in Table 9, the two-stage R717 was the most efficient, although the cascade system came in close.
Although the transcritical system improved performance, the picture remains much the same. The gain seen in the transcritical systems can be attributed to the LT compressors playing a larger role in the total consumption, with the superior COP of the R744 compressors in LT operation accounting for this shift.
4. Optimized system calculations
As we now start to explore the findings for the optimized systems, it's important first to clarify the distinctions between an optimized system and a standard one in this study. Additionally, we'll address some key considerations to keep in mind before delving into the observations and results.
The changes from standard systems (only 300/900kW)
Considerations for optimized systems
Parallel compression is a feature of the simulation software, primarily utilizing MT compressor types.
Again, in relative terms with two-stage R717 as a reference.
It's clear that transcritical systems show more significant gains compared to traditional systems, helping narrow the gap between the two.
As a variation of this result, the transcritical systems were calculated without hybrid coolers while employing all other optimizations. This decision was based on two considerations:
Although the economic calculations did not yield clear results, the full advantage of not running hybrid coolers may not be immediately apparent. Nevertheless, the calculated power relative to the R717 two-stage system is presented in the table and figure below.
5. Concluding thoughts
When analyzing the efficiency data, it is evident that no matter how much a transcritical R744 system is optimized, it cannot compete with a two-stage R717 system. However, it does come relatively close in colder climates. In general, a transcritical R744 system exhibits a 5 to 10% higher energy consumption in colder climates, which increases to around 30% higher in relatively warmer climates.
Cascade systems typically exhibit energy consumption approximately 5% higher than that of the two-stage R717 system. However, it's important to note that the temperature range investigated in this study does not favor the cascade system. In systems with a lower evaporating temperature on the LT (low-temperature) side, the cascade system may eventually become more efficient as R717's efficiency declines rapidly. The two-stage R507 system, included primarily for comparison purposes, generally consumes more power than the two-stage R717, and in the best-case scenarios for transcritical R744, it is roughly equivalent in power consumption.
In the past decade, there have been remarkable advancements in transcritical system efficiency, which is quite impressive. Simultaneously, the R717 (ammonia) proponents have placed significant emphasis on reducing charge, as this is a challenge associated with R717 systems. Consequently, the landscape is continually evolving, and we hope this study clarifies the current status of certain aspects of this dynamic field.
Learn more about CO2 transcritical systems simplified: https://www.danfoss.com/media/m3lb2pl5/forward-1120x720.jpg?anchor=center&mode=crop&width=1050
Get a closer look at transcritical refrigeration: https://www.danfoss.com/media/go5pjq5y/whitepaper-1120x720.jpg?anchor=center&mode=crop&width=1050
Market Researcher & Report Writer @ATMOsphere
5 个月Saroj Thapa
Temporarily retired. Former Facilities Manager at Mary Singleton Jacksonville Regional Service Center, Florida Department of Management Services
5 个月Thank you Danfoss for this very thorough study.
?? Space Enthusiast | Passionate about CFD | Student at PCCOE Pune | Technical Coordinator at ISTE | Former Intern at CSIR-NAL | Student Scout and Guide ??
5 个月This detailed study on industrial refrigeration systems provides valuable insights into efficiency trends across climates and configurations. Very informative! ??
Talent Acquisition Partner-SGP (新加坡-人才招聘合作伙伴) - Lives Empowered, Future Transformed
5 个月Interesting!
Thank you Danfoss for interesting comparisons. It is always interesting to have data analysis and system comparions and there will never be one systems design or refrigerant that fits all needs, but lets keep it natural. 1) Flodded CO2 systems can be compared to a Ultra Low Super heat systems which is the standard design for supermarket and industrial CO2 systems today. In this systems the refrigerant pump energy plus related heat loss in the pump module can be eliminated. This could give 5-10 % system saving. 2) Parralllel compression is the standard today for industrial systems so it should be included also in the floded calculations. It adds another 5% to the efficiency 3) Ejectors are standard in warm climate or it relation with the need for heat recovery. It can be combined with the Ulta Low super heat design. The Danfoss combi ejectors can both pump liquid back to the reciver and move gas so it has double benefit in the system design. It will give another 5-7% efficincy gain. My conclusion is that a fully optimized Ultra low super heat system can outperform a CO2 / ammonia cascade system and have similar efficiency as an ammonia system.