Is it the compressor or the inverter at fault?

Is it the compressor or the inverter at fault?

If you get an error on your air con or heat pump indicating inverter fault / over current etc, (there are loads of fault codes for this) they all mean the same thing. Either the inverter PCB (printed circuit board), the Compressor, or both are knackered. The skill is to work out which one is at fault. Manufacturers will have their own convoluted solutions, some will sell you expensive tools, mine works on every manufacturers kit no matter how big and its cheap.


In fridge parlance we call a compressor "the pot". I used to have a coin with pot written on one side and board on the other, toss the coin and change the one it lands on, if it didn't work change the other too.

This is not far removed from the advice given out to engineers, mostly by people selling parts and idiots. I was always told a bad engineer changes everything, a good engineer only changes the broken bit.

If you know your inverter theory you can take a multi meter and bell out the PWM module on the inverter board to see if its knackered.


But its a bit of a faff and I haven't got time here to tell you how its done.

Likewise the compressor, you can bell it out using a multi meter and a Megger


But who has a megger on the van? and no meter tells you if the compressor is seized or tight.

Years ago you used to be able to buy inverter checkers, a box you plugged the compressor leads into with 6 flashing lights. Total waste of money, they dont work. The inverters are so fast these days they spot the box isn't a compressor so no lights, light up.


So how do I do it?

Simple, lets assume we go to a unit with an inverter fault code, we dont know if the fault is that the compressor is faulty or the inverter is not sending out a proper power supply to the compressor.

I turn off the power, wait 60 seconds so all the boards on the unit have powered down, pull the cables off the suspect compressor and put them onto my trusty little compressor from an old (but working) unit. I just plonk the test compressor on the floor in front of the unit. Mine is a 3kW split system compressor. see top photo. The tubes are bent over almost sealing it up so it doesn't leak oil.

Now I turn on the unit and wait for the compressor to start, I stand at the outdoor unit while I wait. As soon as it spins up, I kill the power with the isolator. I only want it to run for a few seconds,10 at most. If the compressor starts the inverter pcb in the unit is good, the fault lies with the compressor.

If the compressor fails to start and the unit trips on an inverter alarm the Inverter Pcb is faulty and needs changing.

Simple huh? just put another good compressor (or any 3 phase motor) in place of the suspect compressor and test it. Its cheap, it works, and its easy to do.

Its good to remember, faulty compressors dont instantly kill inverter boards, it takes quite a long time for a compressor to kill a board, and these days the inverters are so good they will stop the unit before the compressor has time to do real damage. to the board.

And Faulty inverters dont kill compressors.

Enjoy. Who needs fancy tools when you've got an old compressor from a unit you've ripped out on the van?





Compressors these days use a 3 phase brushless DC motor. 3 phase AC square ("modified sine") wave input apparently. An ordinary Variable Frequency Drive won't work with them.

回复
Roman Mikes

Experienced HVAC & Gas Engineer | Gaspark - Domestic & Commercial Gas Engineer | Specialist in Wall-Hung Gas Boilers, Heat Pumps & VRF Systems | 20+ Years Expertise in Installation, Maintenance & Product Development

2 周

Good evening Graham ,the discrimination is very useful.Would you be kind to help me please.I have Vaillant aerotherm-prox 7 years old with F code 752 and 750 invertor faut /compresor faul. It runs for 2 min and then stops. What would you advise? thank you.Can I call you tomorrow please or my phone number is 07988707561 Roman

回复
Matthew G.

Gas engineer, Electrician

2 周

In the trade we used to know the useless engineers, they would order a fxxk knows kit…

要查看或添加评论,请登录

Graham Hendra的更多文章

  • Does Blogging on Linked-in work?

    Does Blogging on Linked-in work?

    I started writing these blogs on the 3rd Feb 2020 https://www.linkedin.

    35 条评论
  • Screw quiz

    Screw quiz

    I was teaching the other day and it appears my students dont know the difference between the different types of screws…

    22 条评论
  • Frozen heat pump, who pays?

    Frozen heat pump, who pays?

    This week one of my experimental heat pumps split its heat exchanger. "Serves you right you dick, you should have used…

    22 条评论
  • 1/2 price heating

    1/2 price heating

    I've got a heat pump at home, I've had one for years. When I first got one I played around with it a bit to make it…

    18 条评论
  • Low flow, give me strength

    Low flow, give me strength

    Low flow alarms on heat pumps really piss me off. I'm sorry but as soon as a heat pump shows low flow everyone shits…

    38 条评论
  • Open zone, just like the 1970s

    Open zone, just like the 1970s

    At home I have an amazing heat pump from Ideal Heating connected to (and let down by) an open zone heating system. For…

    103 条评论
  • HNY its 2025 the beginning of the era of lower flow rates and smaller pipes.

    HNY its 2025 the beginning of the era of lower flow rates and smaller pipes.

    HNY, welcome back to work, 2025 is going to be a great year for heating technology, there is some really interesting…

    49 条评论
  • Hybrids are back.

    Hybrids are back.

    Hybrids are heating systems where you have a heat pump and a boiler, its a dual fuel solution like a hybrid car. For…

    121 条评论
  • The Graham Hendra Awards 2025

    The Graham Hendra Awards 2025

    Welcome to the 4th annual Graham Hendra awards, a cynical and hopefully light-hearted view of the heat pump industry…

    29 条评论
  • "What a monstrosity, I'm not having that outside my house. "

    "What a monstrosity, I'm not having that outside my house. "

    The first rule of renewables is it has to be ugly, Heat pumps are ugly, solar panels are ugly, need I go on? I love a…

    24 条评论

社区洞察

其他会员也浏览了